Abstract

ABSTRACTThe effects of leakage electric currents in water on the corrosion of heat sinks in high-voltage (±500 kV) direct-current converter cooling systems are presented. An experimental water-cooling setup was established, and simulated operating experiments were conducted. Electrolytic corrosion experiments with aluminium sheets were carried out. Results of the simulated operating experiments reveal that the micro leakage currents which are mostly distributed within a 4-mm-long region inside the heat sinks result in significant corrosion of aluminium under high-voltage operating conditions. Through quantitative and morphological analysis of the electrolytic corrosion experiments, the anodic or cathodic leakage currents through heat sinks are inferred to induce stray-current corrosion or alkaline corrosion, respectively. Additionally, the effects of leakage currents on increasing the alkaline condition are verified. The obtained results indicate the long-neglected impact of leakage currents in HV converter cooling systems and lay the groundwork for evaluation and prevention of corrosion in metal heat sinks.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.