Abstract

AbstractA gas analyzer has been developed using cavity ring‐down spectroscopy (CRDS) technology, designed to simultaneously measure the concentrations of CO2 and CO. These gases are critical indicators of transformer insulation degradation. The analyzer covers a CO2 concentration range from a few ppm to several thousand ppm and can measure CO/CO2 concentration ratios from 0.076 to 0.8. The selected absorption lines for CO and CO2 are centered at 6337.99 and 6338.59 cm−1, respectively. The two candidate lines are proximate to each other and nonoverlapping. The experimental results indicate that the system accurately fits the measured and calculated signals, enabling concentration measurements at the ppm level. This confirms its ability to measure the gas concentrations and ratios critical for assessing the condition of transformer insulation. This CRDS‐based system offers a reliable and sensitive method for early detection of potential transformer faults.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.