Abstract
Optimal design of hybrid renewable mini-grids requires both economic and power quality considerations. Existing modeling approaches address these considerations via separate or loosely coupled models. Here, we extend REopt—a techno-economic optimization model developed at the National Renewable Energy Laboratory—to consider both within a single model. REopt formulates the design problem as a mixed-integer linear program that solves for a site's optimal technology mix, sizing, and operation to minimize life cycle cost. REopt has traditionally assumed a single node system. In the work presented here, we expand the REopt platform to consider multiple connected nodes with associated voltage constraints. In order to do this, we model power flow using a fixed-point linear approximation method. We then use the model to explore design considerations of mini-grids in Sub-Saharan Africa. Specifically, we evaluate under what combinations of transmission line distance and capacity it is technically viable and economically preferable to build multiple isolated mini-grids versus an interconnected, centralized system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.