Abstract

Stationary oxygen concentration in a closed heat-supply system, which is filled and replenished with nondeaerated water at a temperature of 20°C, has been calculated. The calculation takes into account the system surfaceto-volume ratio and the relative added makeup water volume fraction. In the case of a system using corrosion inhibitors, the stable oxygen concentration at a preset makeup rate falls within 400–800 μg/dm3. Experiments performed in a special setup for polarization measurements showed that, at an oxygen concentration of 600 μg/dm3, a decrease in the general internal corrosion rate can be achieved using IOMS-1 and PAF-13A inhibitors at a concentration of 4–5 mg/dm3, or a zinc complex of oxyethylidenediphosphonic acid at 25 mg/dm3.