Abstract
This paper reports a theoretical study of a conventional vapor compression air conditioner combined with a solar energy source. This system comprises two parts: the cooling mechanism and the solar heat source to operate it. Only the cooling machine part will be considered here, in which the refrigerant temperature leaving the immersed coil inside the storage tank can be calculated directly from the pressure–enthalpy diagram of the operating refrigerant. The investigation has been made using a new low global warming potential refrigerant that belongs to HFO family as an alternative to two high global warming potential refrigerants that belong to HFC family. These are R-1234ze(E) as an alternative to R-134a and R-410A. Comparisons between the classical vapor compression air conditioner and the solar assisted air conditioner and also between the selected refrigerants are investigated. The effects of the refrigerant temperature leaving the storage tank on the main performance parameters such as the coefficient of performance, the gain based on compression work, and the required condenser surface area are discussed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.