The effects of static compensation on the voltage stability boundary are investigated. For a class of voltage instabilities which correspond to static bifurcations of load flow equations, minimum singular values of the Jacobian matrix and total generated reactive power are calculated as indicators of stability margin, and sensitivity methods are used for reactive support allocation. Improvement in stability margin under progressive loading was investigated on a 39-bus test system for different allocations and amounts of reactive support with reactive generation capabilities taken into account. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.