Abstract
The common characteristics of a nonlinear system are multiple equilibrium points, limit cycles, jump resonance and sub-harmonic generation. Ferroresonance is also a nonlinear electrical phenomenon, which occurs frequently in power systems including no-load saturable transformers, transmission lines and single/three phase switching. In this work, we modeled the 380kV West Anatolian Electric Power Network of Turkey, by performing numerical simulations using MATLAB-Simulink Power System Block-set. We generated the signals that are characteristics to the ferroresonance in order to exhibit the emergence of the nonlinear phenomenon. In addition, using the continuous wavelet transform (CWT), we observed the behavior of the ferroresonance both in time and frequency domains. Using the results of the CWT and Power Spectral Density (PSD) applications, the ferroresonance is determined from the emergence of the over voltage changes and the inter-harmonics of between 100±Δf and 200±Δf depending on frequency resolution ±Δf.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Electrical Power & Energy Systems
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.