Abstract

Condensing and evaporating heat transfer and pressure drop characteristics of an ozone friendly refrigerant HFC-134a and a HCFC refrigerant R-22, flowing inside a 9.5 mm (3/8 in) OD axially grooved tube were investigated experimentally to obtain the quasi-local heat transfer data and the correlations. When compared to R-22 at the same refrigerant flow rate, the condensing heat transfer coefficients for R-134a are 8 percent to 18 percent higher, and the pressure drop is 50 percent higher. The evaporating heat transfer coefficient with R-134a is about the same for mass velocity below 270 kg/m2-s and decreases above that velocity, relative to R-22. Performance characteristics are compared with data from literature reports.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.