Abstract

The evaporation heat transfer coefficient and pressure drop for refrigerant R-22 flowing in the plate and shell heat exchanger were investigated experimentally in this study. Two vertical counterflow channels were farmed in the exchanger by three plates of commercial geometry with a corrugated trapezoid shape of a chevron angel of 45 ° Upflow boiling of refrigerant R-22 in one channel receives heat from the hot downf1ow of water in the other channel. The effects of the mean vapor quality, mass flux, heat flux and pressure of R-22 on the evaporation heat transfer and pressure drop were explored. The quality change of R-22 between the inlet and outlet of the refrigerant channel ranges from 0.03 to 0.05. The present data showed that both the evaporation heat transfer coefficient and pressure drop increase with the vapor quality. At a higher mass flux, the evaporation heat transfer coefficient and pressure drop are higher for the entire range of the vapor quality Raising the imposed wall heat flux was found to slightly improve the heat transfer, while at a higher refrigerant pressure, both the heat transfer and pressure drop are slightly lower.