Abstract

In this study, external condensation heat transfer coefficients (HTCs) of nonazeotropic refrigerant mixtures of HFC32/HFC134a and HFC134a/HCFC123 at various compositions were measured on a horizontal smooth tube of a 19 mm outside diameter. All data were taken at the vapor temperature of 39 °C with a wall subcooling of 3–8 °C. Test results showed that HTCs of the tested mixtures were 19.4–85.1% lower than the ideal values calculated by the mole fraction weighting of the HTCs of the pure components. A thermal resistance due to the diffusion vapor film seemed to be partly responsible for the significant reduction of HTCs with these nonazeotropic mixtures.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.