Abstract

In the present study, condensation heat transfer and frictional pressure drops of refrigerant R-600a (iso-butane) inside a helically dimpled tube and a plain tube of internal diameter 8.3mm were measured and analyzed. All tests were performed at different vapor qualities up to 0.82 and average saturation temperatures ranging between 38 and 42°C. Refrigerant mass fluxes varied in the range of 114–368kg/m2s. The inner surface of the helically dimpled tube has been designed and reshaped through three-dimensional material surface modifications consists of both shallow and deep protrusions which are placed evenly in helical directions on the tube wall. The experimental results show that the heat transfer coefficients of the dimpled tube are 1.2–2 times of those in smooth tube with a pressure drop penalty just ranging between 58% and 195. The highest heat transfer coefficient is occurred at vapor quality of 0.53 and mass flow rate of 368kg/m2s. On the other hand, the maximum increase of pressure drop takes place at vapor quality of 0.55 and mass flow rate of 368kg/m2s.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.