Abstract

ABSTRACTIn this study, heat transfer coefficients and pressure drops of R-134a inside round and flat tubes are investigated experimentally with mass flux of 450, 550, and 650 kg m−2 s−1 at saturation temperatures of 35°, 40°, and 45°C. The effects of mass flux and saturation temperature on heat transfer coefficient and pressure drop are examined. The maximum enhancement factor and pressure drop penalty are obtained by flat tube (FT-2) up to 2.101 at 450 kg m−2 s−1 and 3.01 at 650 kg m−2 s−1, respectively. The correlation for flat tubes is proposed to predict the heat transfer coefficient within ±20% error.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.