Abstract

The paper reports measured heat transfer and pressure drop data for condensation of propane, R1234ze(E) and R22 in circular (dh=1.085mm) and square (dh=0.952mm) horizontal minichannels. The saturation temperatures are 40°C and 50°C with mass fluxes varying from 200 to 800kg/(m2s) and vapor qualities from 0.1 to 0.9. The experiments investigated the effects of mass flux, vapor quality, saturation temperature and channel geometry on the heat transfer coefficients and pressure drops. The results show that the heat transfer coefficients and pressure drops increase with increasing mass flux and vapor quality and decreasing saturation temperature. The heat transfer coefficients in the square minichannel are larger than those in the circular minichannel. The study shows that propane and R1234ze(E) are good substitutes for R22 based on the condensation heat transfer characteristics. The pressure gradients in the circular and square minichannels differ little for propane with mass fluxes of 200, 350 and 500kg/(m2s) and for R1234ze(E) with a mass flux of 500kg/(m2s). The pressure gradients for propane are larger than those of R1234ze(E) which are larger than those of R22. Condensation heat transfer and two-phase pressure drop correlations were evaluated against the experimental data in the square minichannel.