Abstract

The flash tank separator is one of the most important components that can be used to improve the performance of a refrigeration cycle by separating the liquid from the gas–liquid two-phase flow and providing the evaporator with only liquid refrigerant. This technique increases the effective area and enhances the heat transfer coefficient in the evaporator. To optimize the size of the vertical flash tank separator for obtaining high separation efficiency, the effect of the size of the vertical flash tank separator needs to be considered. This paper investigates the effect of the size on the liquid separation efficiency of the vertical flash tank separator. This paper also assesses the usefulness of Computational Fluid Dynamic (CFD) in flash tank design, and this is achieved through experiments and simulations on a range of relevant configurations using water as the working fluid. The results revealed that the size has a significant effect on the liquid separation efficiency, as the highest value was achieved by the largest size (VFT-V5). The CFD simulations give a good agreement with the experiments; all the simulations underestimated the liquid separation efficiency by approximately 0.02 over the range of conditions tested.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call