Abstract
Three design enhancement options for a vertical gravitational flash tank separator were proposed and investigated in this work. Computational Fluid Dynamic (CFD) was used to assess the optimum configurations of the vertical gravitational flash tank separator. A series of experiments were performed to test the CFD proposed configurations of the enhancement design options. This paper also assessed the usefulness of CFD in flash tank design, and this is achieved through experiments and simulations on a range of relevant configurations using water as the working fluid. The results revealed that the combination of the inlet flow direction and extractor had a significant effect on the performance of the vertical flash tank separator which increased by 2%. The results also revealed that there was a good agreement between the CFD simulations and experiments; the CFD simulations underestimated the liquid separation efficiency by approximately 0.02 over the range of conditions tested.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Air-Conditioning and Refrigeration
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.