Abstract

Up till now inductive voltage transformers are only suitable for measuring harmonics if high measurement errors are acceptable. However, as monitoring frequency harmonics becomes more important, the design of inductive voltage transformers needs to be changed in a way to increase its frequency range. The poles and zero points of the frequency response of voltage transformers can be compensated by using different methods. One possibility is to connect an external capacitance to the half winding in order to compensate the first resonance or to connect it to the quarter of the winding in order to compensate the second natural frequency. Another alternative is to change the winding itself for compensating resonance frequencies without using any capacitances. Finally, it is explained how to minimize the transformation error at frequencies up to 9 kHz.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.