Abstract

This paper compares seven different standards, i.e., IEEE Std. 80, 2000 edition, IEC 60479-1, BS 7354, EA-TS 41-24, CENELEC HD 637 S1, DL/T 621 and ITU-T K.33 used for ground grid design at 161/23.9-kV indoor-type substation in the system of Taiwan Power Company. The calculated results from equations proposed by Sullivan and the Current Distribution Electromagnetic Grounding and Soil structure analysis (CDEGS) software package are also included. The results show IEC 60479-1 gives the lowest limits of tolerable touch and step voltages whereas BS 7354 gives the highest when no chippings on the ground surface are considered. The designed maximum predicted touch voltage obtained from Sullivan’s equation is higher than those obtained from the formulas of BS 7354, EA-TS 41-24, DL/T 621 and CDEGS, the mesh voltage is higher than those from IEEE Std. 80, 2000 edition and CDEGS.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.