Abstract

This paper describes a comparison of results from testing shear strength of autoclaved aerated concrete (AAC) walls strengthened with superficial strengthening with the results of tests of walls made of various types of joints and mortar. The initial and characteristic shear strength and the angle of internal friction were compared. The test elements were made using two types of mortars, three types of joints, and two methods of reinforcement. The models were made using masonry units in the SOLBET OPTIMAL system. SOLBET 0.1 mortar, intended for thin joints, as well as SOLBET SMART polyurethane adhesive were used. Typical joints with a width equal to the thickness of the wall, shell bedded joints and joints without mortar were made. Models with typical joints were also tested as reinforced on one and two sides with the FRCM system, using the mineral cement matrix PBO-MX GOLD MASONRY and the PBO-MESH GOLD 22/22 mesh. A total of 56 models were tested in accordance with the requirements of PN-EN 1052-3: 2004. A significant influence of with superficial strengthening as well as the type of mortar and the construction of joints on the individual parameters of shear strength was demonstrated.