Abstract
In data centers, efficient cooling systems are required to both keep the energy consumption as low as possible and to fulfill the temperature requirements. The aim of this work is to numerically investigate the effects of using partial aisle containment between the server racks for hard and raised floor configurations. The computational fluid dynamics (CFD) software ANSYS CFX was used together with the Reynolds stress turbulence model to perform the simulations. Velocity measurements in a server room were used for validation. Boundary conditions and the load of each rack were also retrieved from the experimental facility, implying an uneven load between the racks. A combination of the performance metrics Rack Cooling Index (RCI), Return Temperature Index (RTI) and Capture Index (CI) were used to evaluate the performance of the cooling systems for two supply flow rates at a 100% and 50% of operating condition. Based on the combination of performance metrics, the airflow management was improved in the raised floor configurations. With the supply flow rate set to operating conditions, the RCI was 100% for both raised floor and hard floor setups. The top- or side-cover fully prevented recirculation for the raised floor configuration, while it reduced the recirculation for the hard floor configuration. However, the RTI was low, close to 40% in the hard floor case, indicating poor energy efficiency. With the supply flow rate decreasing with 50%, the RTI increased to above 80%. Recirculation of hot air was indicated for all the containments when the supply rate was 50%, but the values of RCI still indicated an acceptable performance of the cooling system.
Highlights
The worldwide demand for storage and processing of data has increased rapidly during the last several years and as a result, the quantity and the size of data centers are increasing [1]
The aim of this study is to investigate the effects of using partial aisle containment for the different floor types, i.e., considering both cool aisle and hot aisle containments
The performance metrics Capture Index (CI), Rack Cooling Index (RCI) and Return Temperature Index (RTI) are compared for different confinement strategies and supply flow rates
Summary
The worldwide demand for storage and processing of data has increased rapidly during the last several years and as a result, the quantity and the size of data centers are increasing [1]. The development of sustainable facilities is at the same time very important since their energy consumption is extremely large. In 2012, 1.4% of the total energy consumption in the world originated from data centers [2]. Uninterrupted operation is the most crucial requirement for data centers [3]. Adequate cooling of the servers is very important, while over cooling is a waste of energy.
Published Version (Free)
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have