Abstract

One of the main limitations in using high voltage and medium voltage DC grids is the issues related to the current-limiting devices and circuit breakers. These devices should be able to handle large currents in the normal operation condition and block high DC currents in a few microseconds in the case of DC faults. Moreover, they are required to dissipate huge amounts of energy stored in the transmission line inductances. In this paper, four configurations of DC circuit breakers from three general groups are evaluated and the results are compared in terms of the time required by the breakers to interrupt the current, maximum DC breaking current, rated voltage, efficiency and current state of development. The performance of DC circuit breakers is evaluated when a line to ground DC fault happens in a 9 module/2 terminal DC system. Simulation results were obtained using Real Time Digital Simulator (RTDS) and PSCAD.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.