Abstract
The present study thermodynamically analyse a vapour compression-absorption cascaded refrigeration system (CRS) that uses R407C and H2O-LiBr as refrigerants, to determine the optimal condensing temperature of cascade condenser. The optimum condensing temperature of cascade condenser is found to be 18°C for 83.09 kW refrigeration capacity at an evaporating and condensing temperature of 0.4°C and 46.8°C respectively. The optimum condensing temperature is found, to maximise the rational efficiency of CRS and minimise the total irreversibility of system. Further comparative study of CRS with equivalent vapour compression refrigeration system (VCRS) used for water chilling applications shows that the electric power consumption in CRS is reduced by 70% and COP of compression section is improved by 235% as compared to equivalent VCRS.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Energy Technology and Policy
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.