Abstract

In this paper, a mathematically rigorous method is presented to calculate the impedance of FCLs based on a desirable change of short circuit currents. The method is found on the principle of superposition and can be easily incorporated into standard short circuit current calculations of power systems. The changes of the short circuit currents for each FCL installed are easily calculated without having to build a new impedance matrix for each new case. In addition, the method gives a clear graphical representation of the impact of the FCL on the power system taking advantage of the FCL impedance locus in the complex plane. The resultant plots provide valuable insight and information to utilities, system planners, and FCL manufacturers. FCL manufacturers can use these plots to identify the FCL impedance value and angle subject to the manufacturing and system constraints. The plots also allow utilities and system planners to compute the changes of fault current distribution caused by the FCL quickly and accurately. Results show that FCLs can increase short circuit currents in other branches. High-limiting FCLs may cause larger increase in short circuit currents of other branches and therefore a compromise may have to be made between fault current limitation and the maximum additional currents that are acceptable in other branches. Examples on a three-bus system and an eleven-bus system are presented for illustration and validation.