To obtain realistic data on the high temperature superconducting (HTS) power cable, 3-phase 100 m long, 22.9 kV class HTS power transmission cable system have been developed by Korea Electrotechnology Research Institute (KERI) and LS cable Ltd. that is one of 21st Century Frontier Project in Korea. This cable was installed at Go-chang testing site of Korea Electric Power Corporation (KEPCO). For the application of the HTS power cable joint is very important to ensure the performance. Therefore, this paper gives some investigation of AC loss, critical current and joint resistance in jointed HTS tape. We experimentally showed that the influence of joint resistance on AC loss by using several joint methods. Finally, we are measured critical current, AC loss and jointed resistance for the manufactured mini-model cable.