Abstract
This paper presents the results of research about louvre panels with 4 blades, 5 blades, and 6 blades for mechanical and acoustical performance which installed at the outlet of the ducting system. The mechanical performance will show up the airflow velocity and pressure drop, for the acoustical performance will analysed for its ability to reduce noise in the HVAC System. The measurement method used a rectangular linear duct with the inlet of a fan as an airflow source and loudspeaker as a noise source. The ability tested from the acoustic parameters of TL and the directivity of the noise from the outlet section, as well as mechanical analysis performance based on airflow and pressure drop. For the pressure drop parameter value is up to 20 Pa for 4 blades louvre, and about 24 Pa for 5 blades and 6 blades louvre. By using third octave band filter from 20 to 8000 Hz, the highest TL value is at 27 dB at a frequency of 63 Hz. For the directivity used to determine the distribution of sound energy around the outlet, it shows that the highest SPL value is at a frequency of 1 kHz with the difference from the perpendicular angle of the outlet after being given a louvre acoustic panel of 12 dB. So, the installation of louvre panels has small of pressure drop effect, but it can be effective for noise reduction.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.