Ground source heat pump systems use boreholes to exchange heat with the ground. The thermal performances of ten horizontal boreholes have been evaluated by performing in-situ thermal response tests (TRT) on each borehole. The tests determine both ground thermal conductivity and borehole resistance. Ground thermal conductivity depends on moisture content, which may change with weather conditions for shallow horizontal boreholes. All the boreholes pass through clay soil at a site in Stillwater, Oklahoma (USA). A drought occurred during the two years separating two sets of TRTs. The ground thermal conductivity decreased as much as a factor of 2 in shallower boreholes where depths ranged from 1.9 to 2.3 m. On the other hand, the ground thermal conductivity remained nearly unchanged for two deeper boreholes with depths of 2.9 and 3.4 m. The borehole resistance increased by a factor of 2 for the shallower boreholes, but remained nearly unchanged for the two deeper boreholes. The changes observed in the shallower boreholes would adversely affect a ground source heat pump system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.