CF3I gas, which is one of promising SF6 substitutions, is investigated from the view point of by-product generated in gas discharge, since its global warming potential (GWP) is quite low and its insulation performance is equivalent or superior to SF6 gas. The insulation performance of CF3I gas is examined through measuring sparkover voltage in various electric fields and flashover voltage on the surface of insulating material together with analyzing by-products of CF3I gas. Gas chromatography analysis shows that C2F6, C2F4, CHF3, C3F8, C3F6, and C2F5I are generated by the sparkover and the flashover. The sparkover voltage after 1300 times sparkover in uniform electric field is decreased by 11%. The flashover voltage for a virgin insulator in CF3I gas is almost equal to that in SF6 gas. The flashover voltage in CF3I gas is, however, 0.6 times lower than that in SF6 gas, when the number of surface flashover is increased.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.