Abstract
This paper investigates the performance of a wind-induced natural ventilation tower through an empirical analysis in hot and humid climatic conditions. There are mainly two methods for inducing natural ventilation; namely stack ventilation and wind-induced ventilation. Due to the relatively lower difference between the indoor and outdoor temperature in hot and humid conditions, stack ventilation method alone is rendered insufficient to create desirable air flow between outdoor and indoor building environment to achieve comfort and indoor air quality for the building occupant. Hence, wind-induced ventilation method can be used to achieve the desired air flow rates and improve the indoor air quality for the building. This study revealed that at external wind speed of 0.1m/s, the aerodynamic inverted airfoil roof geometry on the wind-induced natural ventilation tower is able to generate extraction air flow rate of 10,000m3/h with average of 57 ACH to provide comfort and indoor air quality to the internal building environment in hot and humid climatic conditions.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.