Abstract
The operation of the Sylmar HVDC Converter Station has generated interference voltages in the carrier frequency range. Especially a 24 kHz oscillation has caused interference with carrier-type line protection in the ac system as well as with equipment in the station itself. It was shown that the 24 kHz oscillation was caused by a resonance between a RI-filter reactor and stray capacitances in the converter transformers. The comparison between digital simulations and measurements in the station gives a general indication of how complex a digitdl model of a converter station shall be for calculating interference voltages. Such calculationis are expected to be of increasing importance in the future.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.