Abstract

This paper elucidates the question whether bubble effect can possibly take place in the insulation of OIP (Oil Impregnated Paper) type of bushings. The investigations were performed on a bushing insulation model and indicated to a possibility that the effect may occur. Presence of metallic screens in the insulation does not limit the development of gas bubbling; they only force the motion of water vapor bubbles along the model axis. The temperature dependence of bubble initiation on the water content in paper part of the bushing insulation is similar to the presented earlier in literature characteristics for bubbling in main insulation of power transformers. The possibility of bubble effect occurrence may explain the relatively frequent cases of transformer bushing failures.