Abstract

AbstractPower outages can cause harm to both society and individual health. Among the crucial elements of power systems, power transformers play a vital role, and their failures can lead to incidents and disruptions. According to statistics, almost 50% of the explosions and fires in the power transformer are caused by oil‐impregnated paper (OIP) bushing failures. Moreover, moisture is a crucial factor that affects the health of OIP bushings, and assessing the moisture level in OIP bushings is vital to guarantee the safety of power systems. While the frequency‐domain dielectric spectroscopy (FDS) method has been widely used to assess the moisture content of OIP bushings on‐site, it has the disadvantage of requiring a long measurement time. Therefore, a novel technique was proposed in this study that involves measuring the OIP bushing dissipation factor (tanδ) at 1 Hz to estimate the moisture content in a significantly shorter time. Five samples of OIP with various moisture levels have been selected, and an equation based on the OIPs' value of tanδ at 1 Hz was proposed to assess the moisture level of OIP bushings. Furthermore, the validity of the proposed method was successfully verified, proving its precision and time efficiency.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call