Abstract

Calculation of Pressurized Fan Capacity and Static Pressure for Wisma Sudirman Building – Jakarta. A Pressurized staircase is a significant piece of the fire safety strategy of tall structures. Long departure times are repaid by making safe conditions inside departure staircases permitting considering the uprooting time inside those stairs as time where inhabitants can be viewed as sheltered. In accordance with Minister of Public Works Regulation No: 26/PRT/M/2008 concerning Technical Requirements for Fire Protection Systems in Buildings and the Environment, in every building where the occupied height exceeds 24m, each internal fire stair must be pressurized according to the requirements in the regulation. All pressurization requirements for fire stair in this regulation must comply with the applicable standard provisions in SNI No. 03-6571-2001 or latest edition. The capacity and static pressure of the fire stair fan has been calculated for the Wisma Sudirman building, Jakarta, which obtained a capacity of 34,820 cfm and a static fan head of 2.42 "WG.