Abstract

This paper presents a procedure for evaluation of lightning performance of overhead distribution lines. Because both voltages from direct strokes and nearby strokes may cause flashovers in distribution lines, flashover rates due to them need to be analyzed. The procedure is implemented in electromagnetic transient program, and the Monte Carlo method is used to take into account the random nature of lightning parameters. The lightning-induced voltages are calculated with an equivalent circuit derived from Agrawal formula. The influence of insulation level and spacing between surge arresters on lightning flashover rates is analyzed with the procedure. For a line with low-insulation level about 150 kV above high conductivity ground or with high-insulation level about 300 kV above low conductivity ground, the spacing between arresters is best less than 400 m. But for a line with low-insulation level above low conductivity ground, it is better to reduce the spacing to 200 m.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.