Abstract
The overvoltage associated with direct lightning hits has been the important factor for the insulation design of a 6.6-kV distribution line in Japan. In this paper, the flashover rate of the distribution line associated with direct lightning hits is investigated based on numerical calculations and statistical analysis by taking into account the correlation between the peak and the front duration of negative return-stroke current waveforms. When the line is equipped with surge arresters at the interval of 100 or 200 m in addition to the overhead ground wire, the flashover rate associated with subsequent strokes is higher than that associated with first strokes. This demonstrates the importance of the study of current parameters for subsequent strokes. To obtain a conservative estimate of the flashover rate of a line with surge arresters installed every 100 m, calculated for the variable front duration, it is necessary to assume a constant front duration of less than 4 μs and 0.9 μs in the cases of first and subsequent strokes, respectively. With the increase of the installing interval of surge arresters, a constant front duration, leading to a conservative estimate, increases.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.