Abstract
Due to the asymmetry of the traction transformer, there is a problem in the calculation of the measured impedance when the line distance protection on the grid side cooperates with the traction transformer, which causes problems for the setting calculation personnel whether the distance protection can avoid the faults on the other side of the traction transformer. Firstly, the influence of traction substation on distance protection is studied and analyzed. Secondly, the analysis models of single-phase Ii traction transformer, V/v wiring traction transformer and V/x wiring traction transformer are built. Finally, the measurement impedance correction scheme of the protection on the grid side distance after the other side faults of traction transformer is analyzed, and the setting calculation proposal of distance protection is given.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.