Abstract

In order to improve the efficiency of solving the steady-state fault current of the offshore wind farm current collection system, In this method, the equivalent model of the PMSG and the VF control converter is established by taking into account the low-voltage ride-through in the case of failure. The Newton-Raphson method is used to iteratively calculate the fault equivalent network. By establishing a simulation model under PSCAD, the symmetric and asymmetrical faults in the collector system of a grid-connected permanent magnet wind turbine connected to the VSC-HVDC are simulated. Simulation results verify the effectiveness and accuracy of the calculation method.