Abstract
Shell-side heat transfer coefficients of individual tubes for ammonia/lubricant mixture boiling on a 3 × 5 enhanced tube bundle were measured, enabling a detailed study of tube bundle effect under the influences of inlet quality, concentration of miscible lubricant (co-polymer of polyalkylene glycol, PAG), saturation temperature, and heat flux. Tests were conducted in the range of heat flux from 3.2 to 32.0 kW/m 2, simulated inlet quality from 0.0 to 0.4, saturation temperature from −13.2 to +7.2 °C, and lubricant concentration from 0 to 10%. The data show that bundle effect is more significant at a higher saturation temperature. Most of the data in the bottom row are lower than the single-tube heat transfer coefficient data at a low saturation temperature. Lubricant renders the heat transfer coefficient lower in lower rows and higher in higher rows, therefore a larger range of data variation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.