Breakdown and voltage-time characteristics of nonuniform field gaps in compressed SF/sub 6/ gas were studied using a point-to-plane electrode arrangement. Combined voltages, consisting of very fast transient (VFT) overvoltage and standard lightning impulse (SLI) voltage superimposed upon DC voltage, were applied. The experimental gas pressure ranged from 100 to 500 kPa. The results presented show that the magnitude and the polarity of the direct voltage, as well as the gas pressure, influence the corona discharge and the breakdown characteristics. It was found that the breakdown voltages under the VFT are higher than the corresponding values obtained under SLI voltages. At the higher gas pressures, the voltage-time characteristics of VFT fall below those for SLI.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.