Abstract

In a flooded evaporator of an ammonia vapor-compression refrigeration system, boiling commonly takes place with ammonia mixed with compressor lubricant and subjected to a vapor quality at the inlet of the evaporator. In the present study, flooded boiling tests of ammonia on a plain tube under simultaneous influence of a miscible lubricant and inlet quality were conducted. The results suggest that the boiling heat transfer coefficient increases with both saturation temperature and heat flux. The coefficient slightly increases or does not significantly vary with the inlet quality. Heat transfer performance may increase, decrease or demonstrate no change with lubricant concentration, depending on heat flux and saturation temperature. The lubricant effect is generally more significant than the inlet quality effect. A correlation was developed based on the present data for flooded boiling of lubricant/ammonia mixture on a plain horizontal tube under the influence of inlet quality.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.