Abstract

In the present study, tests were performed to investigate the direct expansion evaporation characteristics of ammonia on shell side of triangular pitch plain tube bundle at saturation temperature of −1.7 °C and −20 °C, with heat flux ranging from 5 to 45 kW m−2, and inlet quality from 0 to 30% with exit degree of superheat ranging from 2 to 10 °C. The results suggest that heat transfer coefficient increases with both saturation temperature and heat flux and decreases with degree of exit superheat. The inlet quality effects were more significant at higher saturation temperature than at lower saturation temperature. A correlation was developed for outside boiling of ammonia on plain tube bundle in direct expansion mode with inlet vapor quality and compared with previous pool boiling and bundle correlations with ammonia as a refrigerant.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.