Abstract

This paper presents the results of an investigation on the balcony effect of the fire spread, via external windows, into upper floors. Several natural fire tests were carried out in a compartment that intended to represent a small office and the fire development inside and its spread to the upper floors was analysed. They were tested three configurations of balcony above the exterior window of the compartment; no balcony, a balcony of the same width of the window and a balcony one meter wider for each side of the window. These natural fire tests were also numerically simulated with the Fire Dynamics Simulator (FDS) software and analytically simulated with the simplified calculation methods of annex A and B of EN1991-1.2. The results of the experimental, numerical and analytical tests were compared with each other. The constructive solution for limiting fire spread into upper floors that proved to be more effective was the one with the balcony one meter wider than the window.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.