Abstract
The impact of three different ventilation systems on the temperature and humidity of three similar apartment complexes is investigated in this study. Each complex has six apartments. The ventilation systems are: natural ventilation, mechanical exhaust ventilation, and mechanical supply and exhaust ventilation. The computer controlled data collection system measures the ventilation rate, relative humidity, indoor air temperature, wind speed, wind direction, outdoor temperature, and humidity. The air change rate depends mainly on the habits of the tenants. The mean air change rate of the houses was between 0.1 to 0.8 ac/h. Great daily variation of the air exchange was observed in the data. Negative correlation between relative humidity and ventilation was very significant (p<0.001) in 27 out of 47 cases. Only two cases had very significant positive correlation between ventilation and humidity. Mechanical supply and exhaust ventilation have the greatest variation in ventilation/relative humidity relations.