Abstract

The objective of this study was to determine appropriate values for alkali loading, autoclaving temperature, and autoclaving duration for alkali-silica reaction testing of aggregates in mortar bars. Alkali loadings between 0.52 and 4.5%, autoclaving temperatures from 105 to 130 °C, and autoclaving durations between 5 and 48 h were used. A total of 72 tests involving eight aggregates of various mineralogies and reactivities were performed. Appropriate values for test parameters were found to be: alkali loadings between 3.0 and 3.5%, autoclaving temperatures between 120 and 130 °C, and autoclaving durations between 5 and 12 h for mortar bars, regardless of aggregate type.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.