Abstract

Assessment of the depth of harmonic power penetration in the Nigerian power system with embedded PV is presented. The paper focuses on the investigation of harmonic voltage and current distortions that could be initiated in the Nigerian power system with distributed PV embedded generations. The harmonic power flow and frequency scan were executed on the network at buses of interest. A twenty-four (24) bus of the existing Nigerian grid has been interconnected with five radial feeders each separately terminated with PV generation. The impedance scan results revealed the level of vulnerability of the network to harmonic distortions with volt and current THDs obtained as 12.98% and 58.5% respectively. Finally, a 200kW embedded PV Grid connected system was implemented in MATLAB/SimPower environment to study the impact of the series reactor harmonic mitigating technique on available power transferred from the PV and was found to reduce by 5%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.