Fuel load survey methodology has been recognized to have a significant impact on survey results; however, this impact has not been explicitly quantified. This study seeks to establish a structured approach to validate different fuel load survey methodologies and to enhance and develop guidance on means to correlate the fire load developed using those methodologies. A total floor area of 935m2 in five office buildings was surveyed. The percentage difference in fire load densities obtained from different survey methods ranged between 1% and 50%. This difference has been attributed to the uncertainties associated with the use of each survey method. Statistically, the fire load density was found to be an extreme value (Gumbel) distributed using Kolmogorov–Smirnov test.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.