Abstract
This paper covers the derivation of two sets of short line fault equations for the maximum rate of rise of recovery voltage (RRRV) characteristic of gas blast interrupters. The assumption that the electrical conductivity is proportional to the heat flux potential leads to a integral equation for post-arc current, a critical thermal time constant and the first set of RRRV equations. The assumption that the electrical conductivity varies exponentially with the heat flux potential leiads to the equation and the second set of RRRV equations. For both sets of equations it is shown that the maximum RRRV is (a) approximately proportional to the gas pressure; (b) proportional to the effective nozzle arc length at current zero and the number of series breaks; (c) proportional to temperature dependent coefficients which are functions of gas properties; and (d) inversely proportional to (dI/dt)m where m=3/2 and 1 for the Cassie and Mayr RRRV equations, respectively. These equations are complementary and serve as first-order limits on the interrupting capability of gas blast interrupters.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.