Rapid cycling the compressor of an air conditioning or refrigeration system can be used to modulate capacity, thus offering an alternative to a variable speed compressor. This paper explores design tradeoffs to optimize rapid cycling performance based on experimental results using two different evaporators and changing other components of an air conditioning system. Rapid cycling has inherent compressor lift penalties associated with larger mass flow rates, which need to be minimized. Preventing dryout (superheating) in the evaporator during the off cycle, a major penalty as cycles are lengthened, is also important. Evaporator dryout is minimized by increasing the refrigerant side area and reducing off cycle drainage. Combining a flash gas bypass with a suction line heat exchanger was found to maximize performance during the off cycle while allowing increased cycle lengths without incurring major penalties.