Abstract

The Voltage Source Converter based HVDC (VSC-HVDC) transmission system involving overhead lines lack the inherent ability to overcome severe over currents and over voltages during dc line fault conditions. Presently, the fast acting commercial HVDC circuit breakers are uneconomical and are in prototype status. Due to this, the VSC-HVDC system finds applications in back to back and underground cable transmissions where the occurrence of dc faults is almost zero. In this context, the present paper analyses the combined application of Superconducting Fault Current Limiter (SCFCL) along with Chopper Controlled Resistors (CCR) to overcome and recover from the effects of dc line faults. The resistive SCFCL is modeled in MATLAB and the VSC-HVDC system is analyzed using PSCAD/EMTDC environment. The simulation results show that during dc line faults, the SCFCL is effective in limiting the over currents and the CCR overcomes the over voltages. The combined simulated protection strategy restores the complete VSC-HVDC system without restarting of the dc link.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.