Abstract
The reactor safety circuit considered in this paper is that of a r from m'> design. Such a circuit comprises m guard lines in parallel, continuously monitoring the reactor performance. When r or more lines signal the presence of a dangerous reactor condition the reactor is automatically shut down. Two types of circuit failures are examined, a safe failure which results in a spurious reactor shutdown, and an unsafe failure when no tripping signal can be produced even if the reactor is in a dangerous condition. The repair of a guard line which failed safe starts at once, after the occurrence of a fault, provided that an engineer is available. No circuit failure will occur if the fault is eliminated before r-1 other faults have occurred. The effects of using a single short circuiting facility in the servicing of circuit faults have also been investigated. In this paper formulae for the calculation of the frequency of safe and unsafe circuit failures are derived, treating time as a continuous variable. The results obtained differ from those based on time represented by a series of discrete intervals. Some illustrative examples are given.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.