Abstract
In recent years, as a result of the continuous increase in energy demand, the use of energy storage has become increasingly important. To address this problem, the application of phase change materials (PCM) in buildings has received attention because of their high energy storage density and their ease of incorporation in building envelopes. Despite large experimental works conducted on the application phase change materials in buildings, there is very little work done on this application in combination with night ventilation. In this study, the application of night ventilation in combination with PCM-impregnated gypsum boards for cooling purposes was experimentally investigated. Two identical test huts equipped with “smart” control systems were used for testing the concept. One hut was constructed using impregnated gypsum boards, while the other hut was finished with ordinary gypsum board. Initially an air conditioning (AC) unit, without night ventilation, was used in both huts to charge the PCM during low peak period, showing very little savings in electricity. However, when night ventilation was used to charge the PCM instead, a weekly electricity saving of 73% was achieved.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.