As required by international standards, the distributed energy generators, connected to the grid by an inverter, have to detect an islanding condition within a suitable time interval. In this paper, a phase-locked loop (PLL), based on a third-order prediction-correction filter, is proposed to implement an islanding detector with reduced detection time. Such a feature is obtained using the estimation of the grid angular frequency and acceleration provided by the PLL with a negligible time delay. The proposed approach is implemented on an industrial grade DSP and validated through the experimental comparison among different detection methods, such as rate of change of frequency (ROCOF) and Slip Mode frequency Shift (SMS). The combined use of ROCOF and SMS is also illustrated and discussed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.